Glands for Hazardous areas

A2EX EExde IIC compression gland
for unarmoured cable

Features and Benefits
• For indoor/outdoor use and hazardous areas. (A2E Type)
• Fitted with two specially formulated elastomeric seals. Inner seal seals
  on the cable sheath. Harder outer seal grips the cable, giving superior
  cable retention and IP rating
• Manufactured from high quality brass and nickel plated.
• Supplied with a polypropylene sealing gasket.

 
Technical Data
Type A2EX
Gland Material Brass (Nickel Plated), stainless steel and aluminium*
Seal Material Thermoplastic Elastomer (Silicone on request)
Cable Type Unarmoured
Sealing Area

Outer sheath

Optional Accessories Locknut, Shroud, Earth Tag, Adaptor / Reducer
 
Standards and Certifications

Hazardous Area Classification

 

SANS/SABS IEC, AS/NZS IEC, CNEx

Zone 1, 2, 21 and 22 Exde IIC and DIP

CENELEC / ATEX

Category 2, Category 3, EExde II 2 GD

Compliance Code

Certification No.

CENELEC / ATEX

EN50014:1997E

DEMKO 01 ATEX 130325X

EN50018:2000E

DEMKO 01 ATEX 130325X

EN50019:2000E

DEMKO 01 ATEX 130325X

EN50281-1-1:1999E

DEMKO 01 ATEX 130325X

SANS / SABS / IEC

   

SANS/SABS 1213

SABS S/W 444UX

SANS/SABS IEC 60079-0

2000

SABS S/W 444UX

SANS/SABS IEC 60079-1

2001

SABS S/W 444UX

SANS/SABS IEC 60079-7

2001

SABS S/W 444UX

SANS/SABS IEC 60529

1989

SABS S/W 444UX

SANS/SABS IEC 61241.1.1

1999

SABS S/W 444UX

AUSTRALIAN / NEW ZEALAND / IEC

AS/NZS IEC 60079-0

2000

AUS Ex 03.3844X-1

AS/NZS IEC 60079-1

2001

AUS Ex 03.3844X-1

AS/NZS IEC 60079-7

2001

AUS Ex 03.3844X-1

AS/NZS IEC 60529

1989

AUS Ex 03.3844X-1

AS/NZS IEC 61241.1.1

1999

AUS Ex 03.3844X-1

CHINESE

GB3638. 1-2000 part 1

CNEx09 0429U

GB3638. 2-2000 part 2

CNEx09 0429U

GB3638. 3-2000 part 3

CNEx09 0429U

GB12476. 1-2000

CNEx09 0429U

Ingress Protection IP66/67/68
Operating Temperature -30°C TO +130°C

Special Conditions for Safe Use - X
Glands must be used as part of a certified assembly in surface installations only
Not for use on Exd enclosures that are larger than 2000cm3 volume in group IIC gases in zone 1 areas

 
 

All content copyright © CCG Cable Glands

Western Australia (Perth)
Unit 2, 8 Langar Way, Landsdale, West Australia 6065  :  info@ccgcableglands.com.au
Tel: +61 8 9303 9112  :  Fax: +61 8 9303 2986  : PO Box 285, Joondalup, Western Australia 6919, Australia
Queensland (Brisbane)
Unit 5, 90 Wecker Rd, Mansfield, Brisbane, Queensland 4122, Australia  :  ccgqld@powerup.com.au
Tel: +61 7 3349 9880  :  Fax: +61 7 3349 9847  :  PO Box 3067, Birkdale, Queensland 4159, Australia

Queensland (Townsville)
Unit 4, 58 Pilkington St, Garbutt, Queensland 4814, Australia  : 
todd.ccg@bigpond.com
Tel: +61 7
4779 6133  :  Fax: +61 7 4779 4877  :  P O Box 448, East Garbutt, Queensland 4814

Victoria    Tel: 03 9312 6633 :  Fax: 03 9312 6433
New South Wales   Tel: 02 4961 4433  :  Fax: 02 4961 2498  | Tasmania   Tel: 03 6273 4455  :  Fax: 03 6273 0575